Product Series : Digital Earth Resistance Tester
Earth resistance measurement, Earth voltage measurement
Earth resistance measurement: 0.01Ω~3000Ω
Earth voltage measurement: AC 0V~600V
Alarm function: Setting alarm threshold
Memory: 400 sets of data storage
Large-capacity lithium battery
USB Interface
Product Introduction
ETCR EM3000C Digital Earth Resistance Tester, also known as earth resistance tester, grounding pile type earth resistance, grounding megger, which is used for measurement of earth resistance and earth voltage.The tester adopt with digital and micro-processing technology, and the earth resistance is measured by precision 3-wire method or 2-wire method widely used in industries such as electric power, telecommunication, meteorology, oil field, construction,lightning protection and industrial electrical equipment.
ETCR EM3000C Digital Earth Resistance Tester has unique line resistance verification function, which makes the measurement of low-value earth resistance in the field more accurate, and can avoid errors caused by change in line resistance caused by long-term use of the test line; can avoid errors caused by the test line not being fully inserted into the tester interface or poor contact, as well as the errors caused by the user replacing or lengthening the test line, etc.
ETCR EM3000C Digital Earth Resistance Tester consists of host, monitoring software, test line, communication line, etc.The tester shell adopt with waterproof protection box, which is anti-collision, anti-fall and waterproof (protection level IP65), strong, safe and durable. The tester is also equipped with a large-capacity rechargeable lithium battery set, which is especially suitable for use on outdoor construction site.The host has large LCD display, white screen backlight, and bar chart indication, which is clear and obvious. At the same time, it can store 400 sets of data, realize historical query and online real-time monitoring functions through monitoring software, and dynamically display, with maximum, minimum, and average value indication, alarm value setting and alarm indication functions, and historical data reading, saving, reporting functions, etc.
1.Precision 3-wire method or simple 2-wire method to measure earth resistance.
2. The tester has unique line resistance verification function, anti-interference ability and environmental adaptability, and the On-site low value earth resistance measurement is more accurate.
3. The host has large LCD display, white screen backlight, and bar chart indication, which is clear and obvious.
4. Alarm function, setting alarm threshold.
5. Memory, 400 sets of data storage.
6. USB interface, data upload function.
7. Large-capacity lithium battery.


Technical Parameters
Earth Resistance | Range:0.01Ω~3000Ω | Resolution:0.01Ω | Accuracy:±2%rdg±3dgt |
Earth Voltage | Range:0V~600V AC | Resolution:1V | Accuracy:±2%rdg±3dgt |
Power Supply | DC 7.4V 2600mAh rechargeable lithium battery, battery charge full about 8.4V | ||
Tester Dimension | 280mm(L)X260mm(W)X160mm(H) | ||
Weight | Host: about 4730g; Total weight: about 5kgs(include accessoreies and package) | ||
Measurement Method | Earth resistance: rated current change-pole method, test current 20mA Max; Voltage to earth: average value rectification method | ||
Test Frequency | 128Hz/111Hz/105Hz/94Hz(AFC) | ||
Test Current | >20mA(Sine wave) | ||
Measurement Time | Voltage to earth: 3 times/second; Earth resistance: 15 seconds/time | ||
Data Storage | 400 groups , flash display "FULL" symbol indicate the storage is full | ||
Data Hold | Data hold function: "HOLD" symbol display | ||
Data Access | Data access function: "READ" symbol display | ||
Overflow Display | Over range overflow function: "OL" symbol display | ||
Auxiliary Ground Stake | 2 PCS: Φ9mmX230mm | ||
Test Line | Red 15m, yellow 10m, green 5m, red 1.6m, green 1.6m (total 5PCS) | ||
USB Interface | Equip with USB interface, software monitoring, storage data can be uploaded to computer, saved and printed; Communication cable length:1.5m | ||
Line Resistance Calibration | Avoid errors caused by the test line not fully inserted into the tester interface or poor contact or the user replaces the lengthened test line, ensure earth resistance measurement accurate | ||
Alarm Function | When the measured value exceed alarm setting value, will have “Du--du--du” alarm sound | ||
Automatic Shutdown | 10 minutes without any operation after starting up, the tester will shutdown automatically | ||
Battery Voltage | While battery voltage drop to DC 7.2V±0.1V, low battery voltage symbol“ | ||
Overload Protection | Earth resistance: between each interfaces of E-P,E-C, AC 280V/3 seconds | ||
Protection Level | IP65(close the case) | ||
Working Current | Backlight: 25mA Max; Standby: 25mA Max(Backlight off); Measurement:70mA Max(Backlight off) | ||
Accessories | Tester:1PCS; Ground stake:2PCS; Test line:3PCS; Simple test line: 2PCS; USB communication cable :1PCS; Tool bag:1PC; Special charger:1PCS | ||
Model Comparison
| roduct Pictures | Product Model Name | Resistance Range | Soil Resistivity Range | Voltage Range | Current Range | Alarm Function | Other |
![]() | ETCR EM3000A+ | 0.00Ω~2000Ω | -- | 0~200V | -- | -- | -- |
![]() | ETCR EM3000+ | 0.00Ω~2000Ω | -- | 0~200V | 0mA~100A | -- | -- |
![]() | ETCR EM3000 | 0.00Ω~2000Ω | -- | 0~600V | -- | Yes | Data Storage IP65 |
![]() | ETCR EM3000B | 0.00Ω~30.00kΩ | 0.00Ωm~9000kΩ | 0~600V | -- | Yes | Data Storage IP65 |
![]() | ETCR EM3000C | 0.00Ω~2000Ω | -- | 0~600V | -- | Yes | USB Communications Data Storage IP65 |
![]() | ETCR EM3040 | 0.00Ω~2000Ω | -- | 0~300V | -- | Yes | -- |
![]() | ETCR EM3100C | 0.00Ω~30.00kΩ | 0.00Ωm~9000kΩ | 0~600V | -- | Yes | USB communication Bluetooth communication Data Storage IP65 |
![]() | ETCR EM3200C | 0.00Ω~300kΩ | 0.00Ωm~9000kΩ | 0~100V | 0.00mA~600.0A | Yes | USB communication Bluetooth communication Data Storage IP65 |