Home / Product / Phase Voltmeter/PT Voltage Drop Tester / Wireless Three Phase Digital Phase Voltmeter / ETCR EM4480 Wireless Three Phase Phase Voltmeter
    ETCR EM4480 Wireless Three Phase Phase Voltmeter
  • Product Series : Wireless Three Phase Digital Phase Voltmeter

    • Main Features

      Wireless synchronous measurement of current, voltage, phase, frequency, power, harmonics and other power parameters at different locations in the substation, wireless PT nuclear phase, load test, three-phase imbalance test
      Clamp jaw size: Φ8mm
      Voltage range: AC 0.00V~700V
      Current range: AC 0.0mA~20.0A
      Phase range: 0.0°~360.0°
      Frequency range: 45.00Hz~65.00Hz
      Active power: 0.0W~14kW
      Power factor: -1.000~1.000
      Current vector sum: 0mA~60.0A
      Harmonics: 2~21 times
      PT secondary admittance: 1.0mS~100mS
      CT secondary impedance: 0.1Ω~50Ω
      Storage function: 1000 groups of data storage
      USB communication interface
      Bluetooth communication
      Rechargeable lithium battery

    Product Introduction

    ETCR EM4480 Wireless Three Phase Phase Voltmeter, also known as three-phase power parameter tester, CT load tester, PT load tester, is used for three-phase power parameter measurement, PT wireless nuclear phase, PT load test, CT load test, three-phase imbalance test, harmonic analysis, etc. at different locations in the substation.The instrument consists of 2 handheld terminals, 6 current pliers, 2 sets of voltage test lines, etc. The 2 handheld terminals have wireless communication and GPS communication, and can be set as host or slave to each other to achieve synchronous measurement of current, voltage, phase and other parameters between different locations in the substation. When a single handheld terminal is used, it is used as a three-phase phase voltammeter, which can measure current, voltage, phase, power, frequency, power factor, three-phase imbalance and other parameters and harmonic analysis, and can display vector diagrams of three-phase voltage and three-phase current in real time.When used as a load tester, it can measure the voltage, current, conductivity, admittance, frequency on the PT side, and the voltage, current, resistance, reactance, frequency and other parameters on the CT side. When two handheld terminals are used at the same time, through wireless communication and GPS satellite timing technology, six voltage amplitudes, phases and other parameters can be measured simultaneously at different locations in the substation.Wireless PT nuclear phase can be performed.When the two instruments are turned on at the same time, it is possible to set the wiring type, communication channel, master-slave switching, time setting, etc. in linkage. When four handheld terminals are used at the same time, one of them can be set as the host and the other three as the slave, which is particularly suitable for multi-point synchronous measurement, flexible field application, and more convenient testing.


    ETCR EM4480 Wireless Three Phase Phase Voltmeter adopts a 5-inch touch color screen, Chinese interface, direct function, automatic measurement, easy and fast operation, accurate and reliable, the instrument adopts large-capacity rechargeable lithium battery, with data storage, data access, automatic shutdown, USB interface data upload and export functions.The meter has Bluetooth communication that supports the Android system, and it can be tested on the mobile phone or view the test records.This instrument adopts a special metering chip, which has very high electrical parameter measurement accuracy, can display changes in the parameters to be tested in real time, and has the function of saving data with one key.The product is simple to operate, easy to use, fast measurement, stable, and reliable results. It is a new generation of instruments that specialize in electrical energy metering and relay protection of power systems and conduct on-site testing of secondary circuits. It is also widely used in electrical equipment manufacturing, petrochemical industry, iron and steel metallurgy, railway electrification, scientific research and teaching and other departments.


    1. The stand-alone machine can be used as a three-phase voltammeter, load tester, three-phase imbalance test and harmonic analysis.;
    2. The dual-machine can perform wireless nuclear phase and test current, voltage, phase and other parameters at different locations of the substation.;
    3. When four machines are used at the same time, one can be set as the host and the other three as slaves, which is particularly suitable for multi-point synchronous measurement.
    4. The instrument adopts GPS satellite timing synchronization technology to ensure the accuracy of the PT nuclear phase.
    5. The surveying personnel only need to perform wiring operations, the instrument automatically measures, and the data is updated in real time to facilitate on-site analysis.
    6. The instrument adopts complete isolation technology to avoid safety accidents. 
    7. 5-inch touch color screen, Chinese interface, direct function and simple operation.
    8. Bluetooth communication function.
    9. USB communication interface.
    10. Rechargeable lithium battery.

    EM4480 (9).jpg


    EM4480 (8).jpg

    Technical Parameters


    1.Measurement Range &  Basic Error

    Measurement CatalogMeasurement RangeAccuracyResolution
    Voltage2V~100V±0.3%Fs0.0001V
    100V~700V0.0001V
    Current0.001A~A±(0.3%FS+0.2%rdg)0.0001A
    1A~10A0.0001A
    10A~20A0.0001A
    Harmonics2~21次--
    Phase0°~360°±1°0.1°
    Frequency45Hz~65Hz±0.03Hz0.0001Hz
    Power (include active, reactive, and apparent power)0.002W~1000W±0.3%Fs0.0001W
    1000W~10000W0.0001W
    10000W~14000W0.0001W
    Power Factor-1.000~1.000±0.030.001
    PT Secondary Admittance1.0mS~100mS±0.5%Fs0.0001mS
    CT Secondary Impedance0.1Ω~50Ω±0.5%Fs0.0001Ω


    2.General Specifications

    Power SupplyDC 7.4V 5200mAh rechargeable lithium battery
    Display Mode5 inch touch color screen
    LCD Size108mm×65mm
    Function OptionsTouch screen selection
    Voltage Range0V~700V
    Current Range0.1mA~20A
    Phase Range0°~360°
    Frequency Range45Hz~65Hz
    Power Range0W~14000W
    Power Factor-1.000~1.000
    Harmonics2~21 times
    PT Secondary Admittance1.0mS~100mS
    CT Secondary Impedance0.1Ω~50Ω
    Satellite Timing Accuracy1us
    Satellite Punctuality Accuracy50us (within 60 minutes of disconnection)
    Wireless Communication MethodWireless LORA (230MHz)
    Wireless Communication Distance1000m (in an open place)
    Host Size210mm×129mm×68mm
    WeightHost: about 870g; whole machine: about 5800g (include packing box accessories)
    Clamp Jaw SizeΦ8mm
    Memory1000 sets of three-phase voltammetry tests and 1000 sets of load tests.
    Data AccessYes
    Data UploadUSB interface, test record data is uploaded to the computer, and can be exported to Excel format.
    Battery VoltageThe battery level indicator is displayed, and the battery voltage is reminded to charge in time when it is below 10%.
    Automatic ShutdownAutomatically shut down without operation for 15 minutes after turning on, and remind to shut down before turning off
    Working TimeWhen fully charged, the working time lasts for 12 hours
    Power ConsumptionStandby (backlight is 50): 320mA; work (backlight is 50): 420mA
    Working ConditionsTemperature: -20~50℃, relative humidity: 0~95% HR non-condensing
    Storage ConditionsTemperature: -30~60℃, relative humidity: 0~75% HR


    Model Comparison

    Product Video

    Related Products
    ETCR EM4480 Wireless Three Phase Phase Voltmeter
    • Contact Us

    +86 13802922567 (Johnson Zhang)

    [email protected]

    10th Floor, Block 5, Liandong Intelligent Manufacture Park, No. 105, Shilong North Road, Nanhai District, Foshan City, Guangdong, China

    All Rights Reserved © Guangdong ETCR Electronic Technology CO.,Ltd 2025
    Site Map
    Independent Station